TSYS Group - HQ data center documentation - cooling
Introduction
Cooling is a critical component of any data center. It is often the dominate consumer of energy.
We keep our data center at about 70 degrees F.
Make / model
We have a
- HiSense Portable Air Conditioner (standalone) the manual lists several possible models, unsure which exact one we have. It was about 700.00 at Lowes with a multiple year replacement warranty.
which is rated for:
- 15,000 BTU
It draws about 7 amps when the compressor is running.
With our heat load, the compressor does cycle on/off ,so it keeps cool pretty efficiently from an energy perspective.
Tips/tricks
- Extended exhaust house
We moved the air conditioner to the front of the racks (cold aisle) and extended the exhaust hose todo so.
- Heat barrier
We deployed a cardboard heat barrier above the racks, to keep hot air behind the racks. We also have a vent duct (made of cardboard) to a panel we removed above the doorway.
-
Insulation
- Insulate the exhaust hose!
-
Air movers
- We have a tower fan in the hot row (back), pushing the heat towards the duct.
- We have two small blowers in the cold row (front) helping "kick back" the air blowing from the HiSense.
Instrumentation
We use:
- temper usb probe
- lm-sensors
- DRAC
all consumed via SNMP by librenms to monitor/alert on temperature.This lets us find hot/cold spots across the racks and make any necessary adjustments.